Modscan 64 Bit Software Free Download Updated FREE

Modscan 64 Bit Software Free Download

Overview

Modscan32 is a 32-bit Windows awarding (Modscan64 is similar, only for 64-flake Windows) that serves as a Modbus master device for protocol testing and performing Modbus serial and TCP/IP data collection by polling at user-divers intervals down to milliseconds. It can acquire data in integer, unsigned decimal, and floating point formats. It likewise supports annals writes. The slave response time and delay between polls are user selectable.

Continental Control Systems does sell whatever software products. Please contact the manufacturer directly for information on their various versions and pricing.

More details may be found at the following links:

  • ModScan32 Awarding Clarification
  • Download evaluation software—fully functional, limited-time free demo

Modscan32 is available in a couple of different versions. Contact WinTECH Software Pattern to buy this software. The cost is $65 for the unmarried-user basic version; or $110 for the Professional version that includes MMI (e.grand. trend graphs) and OLE features for Modscan32 data access by Excel's VBA macro language.

For more information on using Modscan32 with the WattNode® Modbus® meter see WNC Modbus Customer Questions.

Pros

  • Supports Modbus/TCP, Remote Telnet Server (for Ethernet/RS-485 SDAs) and a variety of other connexion types (including Telnet) equally well equally straight serial port (COM port) connections.
  • Has optional handshake line control which may exist needed for older RS-232/RS-485 adapters used on legacy PC series ports that don't handle RS-485 bus driver control automatically.
  • Has a "hex dump" display style which is useful for trouble-shooting communications problems.
  • It tin can be quickly set up to read a range of registers of the same type (vs. Ocean Controls approach of setting up individual tags which is more than tedious and time-consuming).

Cons

  • Modscan32's Betoken Blazon selection defaults to "Coil Status" which requires switching information technology to "Holding Register" before a WattNode meter'south register can be polled.
  • Modscan32 is a tool intended mainly for engineers and IT folks who are familiar with the basics of protocols similar Modbus.
  • Captured text files are not in standard CSV (Comma Separated Values) format. The non-standard information format requires using Excel'due south Import Wizard which takes more steps. However, there is a work-around for this (run across csv.exe beneath).
  • Poor trend graphing capability. Difficult to prepare up and alter.
  • When trying to modify a value, the focus doesn't start in the value text box, requiring an actress click.
  • When displaying floating point values, if the window isn't tall plenty, Modscan32 displays multiple columns, but the text from one column overlaps the next.
  • When displaying floating point values, Modscan32 displays blank lines between every other value.
  • Runs merely on Windows. No Linux or Apple Bone version is available.

Quick Start Guide

This section describes how to connect and configure a WattNode meter with Modscan32, set the CtAmps , and brand some basic measurements.

It too discusses how to apply ModScan32 to communicate with WattNode meters via the 2 most common types of SDA (Serial Device Adapter):

  1. A USB/RS-485 adapter.
  2. An Ethernet/RS-485 adapter.

ModScan32 is for polling and recording data readings from slave devices that employ the Modbus communications protocol. It tin also write to registers to configure settings in Modbus slaves. The costless demo version can be useful for isolating the cause of problems when a customer is using another tertiary-party Modbus master program that is misconfigured or that has a software bug by allowing them to compare the readings acquired with their software versus the readings acquired with ModScan32. ModScan32 can also serve as a simple data logger for capturing data in text files. Since the demo version can exist freely distributed, an installer tin use information technology for the minute or two that information technology takes to configure the CT amps ratings via the WattNode meter's CtAmps registers and to verify that the Modbus communications is working.

ModScan32 runs on most versions of MS Windows, including Windows XP. ModScan32 tin communicate with the Modbus WattNode meter using SDAs that support RS-48.

WinTech'southward time-express gratis demo version of ModScan32 runs for a couple of minutes, which is long plenty to configure a WattNode meter's CtAmps registers. To eliminate the time limit, the demo tin be registered past inbound a license primal obtained from WinTech. Every bit of Q3 2009, the basic version costs $65 and the Pro version costs $110. Both versions of ModScan32 support viewing and updating numeric register values and capturing data to text files that can be imported into spreadsheet programs like Excel. The Pro version includes boosted features that support viewing the information every bit trend lines on simple graphical charts and exporting data to OLE client programs. Installing information technology is as simple as downloading the free demo Modscan32.zip file and copying its contents into a folder named, "C:Modscan32".

How to use Modscan32 with a COM port to Configure the WattNode meter's CT Amps Settings

The installation details for USB/RS-485 adapters varies depending on the item model but the primary steps are the same regardless of model.

There is a video-only (no sound-rail) that illustrates this procedure at http://world wide web.youtube.com/lookout?5=QRiGhUDisRg :

  • Connect power supply if needed. Note that well-nigh USB/RS-485 adapters are powered by the USB host and do not crave an external power supply.
  • Insert the adapter. Windows "New Hardware Device Wizard" should appear and prompt for the location of the device driver files which are usually on the software distribution CD that came with the adapter.
  • After following the prompts, if the adapter driver installed correctly, y'all should run across information technology listed nether the Windows Device Director's Ports (COM & LPT) list. Normally it will include "RS-485" in the name. Annotation the COM port number that Windows assigned to the device.
  • Apply Windows Explorer to view the folder where Modscan32 is installed and showtime Modscan32 past double clicking the Modscan32.exe executable.
  • In one case Modscan32 starts upwards a "Modsca1" document window should appear. Enter the WattNode meter'south slave address (set with the DIP switches) in the "Device Id" box. For instance if the meter'southward DIP switches 2 to 7 are off and 1 is on, enter a value of i.
  • Next specify that you desire to read the CT Amps registers: Under "Modbus Point Type", select "Belongings Register". Under "Address" enter "1603". Nether "Length" enter "4". This selects the global CT Amps annals CtAmps and the CT Amps registers for each of the iii phases ( CtAmpsA , CtAmpsB , and CtAmpsC ).
  • Select "Connectedness->Connect" and under "Connect Using", select the COM port number of your adapter and make sure the baud rate matches the WattNode meter'south (9600 if DIP switch 8 is off; 19200 if it is on). No hardware flow command is needed for nigh USB/RS-485 adapters which have the "machine-enable" feature.
  • Click the "Protocol Selections" button and make certain that the "Transmission Fashion" is set to "RTU". The "Slave Timeout" should be "1000 ms". and for the "Delay Between Polls", 500 ms. is a reasonable poll rate.
  • Close the dialogs by clicking the "OK" button and at that signal, Modscan32 should start polling the WattNode Modbus meter. The "Number of Polls" volition showtime incrementing and if the RS-485 interface is properly continued to the adapter, the "Number of Valid Slave Responses" should increment at the same charge per unit.
  • To gear up the CT Amps settings to different values for each of the three phases, double-click on the displayed register which will pop upwards a "Write Register" dialog that allows you to enter the new value. Enter the CT rating in amps and click "Update". The dialog will close and the displayed value of the corresponding CT Amps register should modify accordingly.
  • If the CT rating is the same for all three phases, you can set up all three to the same value at once past writing to the Global CT Amps register (1603).
  • When you are washed you can select "File->Relieve Equally" and specify the file name "CtAmps" to save the changes you made so the side by side fourth dimension you lot run Modscan32, you can select "File" and click on "CtAmps" so you don't have to re-enter the aforementioned register addresses etc. again.

How to Read All WattNode Registers Using Preconfigured Modscan32 Certificate Files

Since there is no universal standard for mapping Modbus register addresses onto specific slave device readings (because the Modbus standard only specifies the low-level communications information transport layer, not the high-level application layer or data types), some customization is required in order to specify which data registers should be polled from a specific slave device and how the information should be formatted. ModScan32 saves this configuration data in special "documents", where each document corresponds to a continuous serial of Modbus holding registers. Each certificate window displays register data of the aforementioned type and format (floating point or 16-bit integer etc.).

To salvage fourth dimension in configuring Modscan32, preconfigured ModScan32 documents are available from CCS in a ZIP annal file named, "Modscan32ForWattNode.zero". These files are preconfigured for acquiring the specific registers containing the WattNode meter data and assume that the meter is assigned a slave address of 1 and that its baud rate is set to 19200 (i.e. the meter'due south DIP switches ane and eight are on, and 2 to 7 are off). The WattNodeAutoStart.tst Auto-beginning configuration file assumes that the USB/RS-485 adapter is assigned to the PC'south COM10 serial port (this can hands be changed as described below). The contents of the Modscan32ForWattNode.zip file should be copied to the same folder, "C:Modscan32", that you created with Windows Explorer when you installed Modscan32.

There are vii custom configuration files for the WattNode meter:

  • Ms32frm.cfg " This file tells Modscan32 to automatically load the configuration contained in the WattNodeAutoStart.txt file at offset-up.
  • WattNodeAutoStart.tst – This is the Auto-start configuration file that tells Modscan32 which COM port the meter is connected to and which documents to automatically open when information technology starts upwards.
  • WattNodeBasicFloatOutputs – This Modscan32 certificate displays energy, power and voltage bladder registers 1001 to 1034.
  • WattNodeAdvancedFloatOutputs – This Modscan32 document displays advanced energy, power and demand float registers 1112 to 1176.
  • WattNodeConfiguration – This Modscan32 certificate displays configuration integer registers 1601 to 1621.
  • WattNodeCustomerDiagnostics – This Modscan32 document displays client diagnostic integer registers 1707 to 1722.
  • WattNodePowerTrendGraph – This Modscan32 certificate displays the phase A, B, C and Need ability float registers (1011, 1013, 1015 and 1169) as ruddy, green, blue and violet traces, respectively on a tendency graph.

After copying the WattNode meter configuration files from the Modscan32ForWattNode.zip file into the same C:Modscan32 folder that you installed the Modscan32 programme (overwriting the existing configuration files), you can launch Modscan32 by double-clicking on Modscan32.exe. Upon launching, Modscan32 volition display some "Registration" dialog boxes. After clicking "OK" to each dialog, Modscan32 will and so try to connect to the meter and if successful, it will display and update the five documents listed in a higher place with new data every 2 or 3 seconds.

If your USB/RS-485 adapter has been assigned to a unlike COM port then an mistake message will announced that says, "Connection Failed!". In that example, you demand to tell Modscan32 which COM port to use by clicking the Connection menu bar particular and selecting the "Connect" item from the list. A dialog box that appears with a "Connect Using:" listing box that allows y'all to select the proper COM port (Annotation: The Windows Device Managing director applet displays all serial COM ports nether the Ports device group). After you've selected the right port, click OK and Modscan32 should then kickoff polling the WattNode meter and updating the displayed documents later on a few seconds.

If your meter uses a CT rated for other than the default of five amps, you can reconfigure it for the proper CT rating by clicking on the WattNodeConfiguration certificate view. Integer register 1603 is the global CT amps register which allows you to set the CT rating for all three phases if they all accept the same rating. In cases where differently rated CTs are used on each phase, registers 1604, 1605 and 1606 permit assigning each CT amps rating for phases A, B and C respectively. If any phase inputs are not used and are left unterminated (no shorting wire) then they can cause small but unwanted energies to be accumulated due to devious electrical fields. This can be prevented by setting their CT amps register to zero, including the global CT amps register (Annotation: The phase LEDs may nonetheless occasionally flash ruddy merely no free energy is accumulated if the CtAmps register is zero).

To modify the value of a register, double-click the displayed register value and a dialog box volition appear that lets you enter the new value. After entering the new value, click the "Update" button and the new setting will be written to the meter.

Modscan32 can log the data readings for whatever of the displayed documents into text files consisting of infinite-separated values. This is done by clicking on the certificate to bring it to the foreground and and so selecting "Setup" from the menu bar and so "Text Capture". A "Save As" dialog will appear that allows yous to specify the text file proper noun and location. Afterwards specifying the file proper noun, another dialog will announced that lets you choose how ofttimes to archive the data. To stop collecting WattNode data, select "Setup" so "Capture Off". Annotation that you tin can specify a unlike data file name and start and cease logging information separately for each document. Since the data is captured as a text file, you should utilize the "txt" file name extension for information file names. To import a captured text file with Excel, select "Open" and scan to the Modscan32 binder and select Excels dialog pick containing "*.txt" from the "Files of Blazon" listing box. A dialog will announced that lets you tell Excel exactly how to import the data. Select the "Delimited" option and click "Side by side"; then check the "Space" box and Excel presents yous with an example of the data that permits selecting columns y'all don't want to import (e.m. the redundant date fields). After y'all click "Stop" the data will exist imported into the spreadsheet.

If you're familiar with how to run Windows console applications, you can utilize a utility called csv.exe (included in the zip file below) that converts from Modscan32'south data format into standard comma-separated values (CSV) format that can be pulled into Excel without using the Excel information import magician. The csv.exe utility processes a information file you previously captured with Modscan32 and converts information technology to CSV format that Excel automatically recognizes.

Whenever y'all change the Modscan32 "Connection" settings yous should relieve them to the WattNodeAutoStart.tst Car-start configuration file by selecting "Connectedness", "Auto First", "Relieve Config" and selecting the WattNodeAutoStart.tst file proper name. This way, the next time yous launch Modscan32, information technology will be able to restore the same communications connexion automatically.

The appearance of the WattNodePowerTrendGraph document can be customized by right-clicking it. A Trend Chart Properties dialog will appear that lets you customize the trace (or pen) colors and assign a information register source to a detail trace. Individual traces can be enabled or disabled past clicking the corresponding pen button and checking or united nations-checking the Enabled box. The register address is entered in the "Signal Accost:" field. The format of the data under the "Format" list box should match the type of register you want to assign to the trace. It is easiest to use the WattNode bladder (vs. integer) registers for trend graphs (and also for capturing data readings to text files). After making changes to the trend graph you should save them by selecting "File" and "Relieve" so information technology will reappear the same way the next time yous start Modscan32.

To add a new Trend Chart, click "File", "Custom Course" and "Create". Then use the mouse to define a rectangular region for the MMI object in the document that appears. Click on the bespeak where you desire the upper left corner to announced and while holding downwardly the mouse button, drag the cursor to the lower correct manus corner. A "Custom Display" dialog box will and so announced that lets you lot select the "Uncomplicated Trend Nautical chart". You tin can then right click the resulting chart to customize the "Pen" attributes that decide the displayed traces.

How to use Modscan32 with an Ethernet/RS-485 Series Device Adapter

The post-obit describes how to connect to a WattNode meter using an Ethernet/RS-485 SDA. Y'all can ignore this section if yous are using a USB/RS-485 adapter. Since the WattNodeAutoStart.txt Car-get-go configuration file was set up up for a USB/RS-485 adapter on the COM10 port, the "Connexion Failed!" mistake message will appear when you lot launch Modscan32. To fix this, select "Connect" and under the "Connect Using:" list box, select "Remote TELNET Server" and enter the TCP/IP address and port of your SDA in the "IP Address:" and "Service Port:" boxes, respectively. These values should match the ones you assigned to your SDA. Refer to your SDA manual for the procedure for assigning the SDA address, port and serial communications parameters. This is usually done with a Web browser but the exact details vary depending on SDA make and model.

Summary

Modscan32 is a simple but useful program and the toll is reasonable compared to almost SCADA or Data Logger software. If you just need to employ it for a infinitesimal or two for assigning the CtAmps configuration registers then the free demo version should exist adequate. Modscan32 will work with any Modbus slave device that conforms to the Modbus communications protocol (come across http://www.modbus.org). By using it in conjunction with the Modscan32 configuration files provided by CCS, information technology provides a quick, vendor-neutral style to verify that a ability monitoring installation with Modbus WattNode meters is working properly.

The figure below shows how Modscan32 presents the WattNode meter information in both numeric and graphic form:

Modscan32.png

The WattNode configuration files for Modscan32 are contained in a unmarried ZIP file: Modscan32FilesForWattNode.zip

Encounter Besides

  • Modbus Software

Keywords: Modscan, Win-Tech, RS485, EIA485, Eia-485